Refrigerated Air Dryer Explained: Working Principles and Key Components

refrigerated air dryer

Table 1 – Typical technical data for a medium industrial refrigerated air dryer (indicative ranges)

ParameterTypical range / valueComment
Nominal flow capacity100–2 000 Nm³/h (≈ 60–1 200 scfm)Larger frames built as multiple parallel circuits
Operating pressure range4–14 bar(g)Check maximum allowable working pressure on datasheet
Rated inlet air temperature35 °CHigher inlet temperature reduces effective capacity
Usual ambient temperature range5–40 °CAbove ≈ 35–38 °C, condenser derating is significant
Typical pressure dew point+2 to +7 °CCorresponds roughly to ISO 8573-1 water class 4–5
Residual water at 7 bar(g)≈ 0.005–0.008 kg/m³> 90–98 % of inlet moisture removed
Pressure drop through dryer0.15–0.30 barAim to keep system treatment losses below ~0.5 bar total
Dryer power (order of magnitude)0.08–0.15 kWh per Nm³/min of rated flowStrongly load- and design-dependent
Typical electrical supply230 V 1-ph or 380–460 V 3-ph, 50/60 HzFollows local grid standards
refrigerated air dryer